Abstract

In recent years,increasingly tripping accidents of transmission line caused by forest fires threatened safety and reliable operation of power grids seriously.Although a large amount of simulation tests have been carried out to study breakdown characteristics of transmission line under fire conditions in China and abroad,there is no uniform standard for voltage application.In order to provide a reference for test standard of gap breakdown characteristic under fire conditions,both uniform voltage rising mode and combined mode of voltage rising and withstand were used to carry out AC breakdown characteristic tests of conductor-plate gap with forest fire simulation test platform.Experimental results showed that,under these two voltage application modes,breakdown voltages were U-type curve distributed with time; breakdown voltages were nonlinearly declined with increase of combustion intensity; as combustion intensity was stronger,voltage application modes had little effect on gap breakdown characteristic according to comparative analysis of breakdown voltage and leakage current characteristic under these two voltage application modes.Combining with actual forest fire feature,combined mode of voltage rising and withstand was recommended to carry out AC breakdown characteristic test of conductor-plane gap under fire conditions.
Translated title of the contributionStudy of Influence of Voltage Application Modes on AC Gap Breakdown Characteristic Under Fire Conditions
Original languageChinese
Pages (from-to)1576-1581
Number of pages6
JournalDianwang Jishu/Power System Technology
Volume40
Issue number5
DOIs
StatePublished - 5 May 2016

Funding

高等学校博士学科点专项科研基金(20120141120027);中央高校基本科研业务费专项资金(2015207020201)~~;

Indexed by

  • EI
  • Scopus
  • CSCD

Fingerprint

Dive into the research topics of 'Study of Influence of Voltage Application Modes on AC Gap Breakdown Characteristic Under Fire Conditions'. Together they form a unique fingerprint.

Cite this