Skip to main navigation Skip to search Skip to main content

基于场路结合法的500 kV线路绝缘子串分布电压的计算

Translated title of the contribution: Calculation of the Voltage Distribution of Insulator Strings in 500 kV Lines Based on the Combination of Electrical Field and Road
  • 李 家靖
  • , 董 振
  • , 曲 锴
  • 武汉理工大学机电工程学院

Research output: Contribution to journal › Article › peer-review

7 Scopus citations

Abstract

The voltage distribution of high-voltage line insulator strings is extremely uneven and difficult to measure.This paper presents a new method for calculating the voltage distribution of insulator strings. This method calculates the insulator stray capacitance by Maxwell capacitance matrix and then substitutes it into the equivalent circuit of the insulator string for calculation. It is more comprehensive and more accurate than traditional methods. Through this method,the voltage distribution of insulator strings in a 500 kV line is simulated and the result is in good agreement with the actual measurement through experiment and it is more accurate than traditional circuit method. It is proved that the algorithm is feasible. Use this algorithm to calculate the influence of insulator deterioration at different positions of 500 kV line on the voltage of insulator strings. It is pointed out that the current method of deteriorating insulators may cause missed judgments.
Translated title of the contributionCalculation of the Voltage Distribution of Insulator Strings in 500 kV Lines Based on the Combination of Electrical Field and Road
Original languageChinese
Pages (from-to)21-26
Number of pages6
JournalGaoya Dianqi/High Voltage Apparatus
Volume54
Issue number8
DOIs
StatePublished - 16 Aug 2018

Indexed by

  • Scopus
  • CSCD

Fingerprint

Dive into the research topics of 'Calculation of the Voltage Distribution of Insulator Strings in 500 kV Lines Based on the Combination of Electrical Field and Road'. Together they form a unique fingerprint.

Cite this