Abstract
The output impedance of a grid-connected inverter is an important parameter to determine the stability of its operation in the grid. It is usually measured by the harmonic current injection method. However, the background harmonics of the inverter may affect the accuracy of measurement results. The non-integer harmonics current injection method can effectively avoid this problem. Since the actual grid operating frequency fluctuates within a certain range, it is difficult to synchronize when using a harmonic current source to inject a non-integer harmonic current, and the method may cause measurement errors. Aiming at the above problems, this paper uses the equivalence of voltage disturbance and current disturbance, and proposes a method to measure the impedance of inverters by a voltage disturbance source. The voltage disturbance source can generate the fundamental frequency and non-integer harmonic voltage to measure the impedance of the inverter, and hence the accuracy of the impedance measurement is improved. The full-band impedance of the inverter is obtained by interpolation. The proposed measurement method is verified by the real-time digital simulation.
| Translated title of the contribution | Measurement Method of Inverter Output Impedance Based on Voltage Disturbance Source |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 4739-4750 |
| Number of pages | 12 |
| Journal | Diangong Jishu Xuebao/Transactions of China Electrotechnical Society |
| Volume | 34 |
| Issue number | 22 |
| DOIs | |
| State | Published - 25 Nov 2019 |
Funding
国家自然科学基金(51777145);国家电网公司总部科技项目“配电网电能质量干扰源接纳能力评估及有源型治理设备入网检测关键技术研究”资助;
Indexed by
- EI
- Scopus
- CSCD
Fingerprint
Dive into the research topics of 'Measurement Method of Inverter Output Impedance Based on Voltage Disturbance Source'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver