Abstract
The SF_(6)gas leakage at the seam of flange of GIS busbar connection enclosure for one EHV 500 kV substation is performed and the cause of the fault is clarified.The cause of the gas leakage generated at the seam of the flange of the connection enclosure is discussed from the aspects of material performance,welding process and structure factor and by such technical means as macroscopic inspection,spectral analysis,penetration testing and ultrasonic testing,finding that the seam of enclosure flange with gas leakage has welding porosity.The results show that the primary reason causing gas leakage of seam of enclosure is due to the porosity defect during the welding period,which is not removed due to not performing surface defect detection test before delivery test.The secondary reason is that the connection of the porosity each other under the action of displacement of the enclosure busbar.Based on these results,the corresponding preventive measures are proposed.
| Translated title of the contribution | Study on Gas Leakage of GIS by Welding Porosity |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 211-215 |
| Number of pages | 5 |
| Journal | Gaoya Dianqi/High Voltage Apparatus |
| Volume | 59 |
| Issue number | 3 |
| DOIs | |
| State | Published - 1 Mar 2023 |