Skip to main navigation Skip to search Skip to main content

电网电压不平衡时双馈感应发电机的运行特性

Translated title of the contribution: Operating characteristics of double-fed induction generator under unbalanced grid voltage
  • 陈 婷
  • , 洪 波
  • , 崔 雪*
  • , 郭 晓云
  • , 刘 会金
  • *Corresponding author for this work
  • 三峡大学电气与新能源学院

Research output: Contribution to journal › Article › peer-review

Abstract

A mathematical model of double-fed induction generartor (DFIG) under the unbalanced grid voltage is built in the positive and negative rotary coordinates. On this basis, the equations of output pow- er, electromagnetic torque and voltage and current in the grid side converter under the unbalanced grid voltage are deduced. The operating characteristics of DFIG under unbalanced grid voltage are studied. The research results show that the negative sequence component of grid voltage could have impact on double-fed generator, including that the second harmonic wave of electromagnetic torque occurs; and the active power of stator output is in fluctuation o( even times frequency. The AC side of the grid side converter produces odd harmonics while the DC bus produces even times harmonics. The simulation results prove the validity of the theoretical analysis.
Translated title of the contributionOperating characteristics of double-fed induction generator under unbalanced grid voltage
Original languageChinese
Pages (from-to)86-91
Number of pages6
Journal武汉大学学报:工学版
Volume48
Issue number1
DOIs
StatePublished - 1 Jan 2015

Funding

国家自然科学基金项目(编号:51177112)