Abstract
Applied in the grid-connected inverter, the internal-model based repetitive control usually features that the delay time is designed according to the nominal grid-frequency. When the grid-frequency deviates, the high-gain pass-bands of the conventional repetitive control will deviate the frequencies of actual fundamental and harmonic currents Consequently the steady accuracy will degrade. This paper proposes a multi-internal-model repetitive control, with ancillary repetitive control loops considering the deviation of grid-frequency parallel embedded. The weight coefficients for the ancillary loops are designed based on the stability analysis of the multi-internal-model repetitive control in frequency domain. From the simulation results, compared with the conventional repetitive control, the proposed control features an equal steady accuracy in the nominal grid-frequency and a developed steady accuracy when grid-frequency deviates, and consequently an improved quality of the current into grid.
| Translated title of the contribution | A multi-internal-model repetitive control for grid-connected inverter considering grid-frequency deviation |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 144-149 |
| Number of pages | 6 |
| Journal | Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control |
| Volume | 44 |
| Issue number | 21 |
| DOIs | |
| State | Published - Jan 2016 |
Indexed by
- CSCD
- Scopus
Fingerprint
Dive into the research topics of 'A multi-internal-model repetitive control for grid-connected inverter considering grid-frequency deviation'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver