Abstract
In view of insufficient dielectric online detection technology of existing minimum oil electrical equipment,in recent years,some scholars have proposed pressure⁃based online monitoring technology of minimum oil equipment.However,internal pressure variation characteristic of minimum oil equipment at overheat defect has not been experimentally studied by scholars.In this paper,110 kV oil immersed vertical currnt transformer is taken as prototype to study by experiment the internal pressure variation characteristic of minimum oil equipment at the tempera⁃ture of 100℃,150℃,200℃,250℃and 300℃respectively.It is shown by the result that①the pressure varia⁃tion by mild and low temperature overheat defects is small and the maximum increments in 50 hours is 1.33 kPa,1.65 kPa,2.01 kPa,2.51 kPa,and 2.70 kPa,respectively;②the pressure variation due to overheat defect shows expo⁃nential increase.In the initial 10 hours,the pressure rises sharply and gradually in 10~20 hours.The pressure re⁃mains basically unchanged after 20 hours.③The increase range the maximum pressure with 50 hours is several hun⁃dreds of Pascals at every 50℃rise in the temperature of the overheat spot.At the same time,three reasons with differ⁃ent pressure variation characteristic due to overheating and discharge defects are pointed out by theoretical analysis.
| Translated title of the contribution | Study on Pressure Uariation Characteristics of Oil⁃minimum Equipment Under Overheat Defects |
|---|---|
| Original language | Chinese |
| Pages (from-to) | [99]-[104] |
| Number of pages | 6 |
| Journal | Gaoya Dianqi/High Voltage Apparatus |
| Volume | 57 |
| Issue number | 8 |
| DOIs | |
| State | Published - 16 Aug 2021 |
Funding
国家电网公司科技项目(52199918000A)~~;
Indexed by
- Scopus
- CSCD
Fingerprint
Dive into the research topics of 'Study on Pressure Uariation Characteristics of Oil⁃minimum Equipment Under Overheat Defects'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver