Abstract
The errors of high voltage direct current(DC)electric energy metering system are mainly composed of DC voltage transformer,DC current transformer and DC electric energy meter.This paper analyzes the relationship between the total measurement error and each link error of the system,and it is found that the total relative measurement error is the sum of the relative errors of each link.Therefore,the voltage divider and shunt with large error should be improved.Through sensitivity analysis,it is found that the parameter that has a great influence on the voltage division ratio of the resistance-capacitance voltage divider is the equivalent resistance of the remote module,and it is taken as the object of improving the error of the voltage divider.The manganin alloy temperature coefficient,which has a great influence on the diverter error,is selected as the object of diverter error improvement.Simulation results show that the optimization of these parameters is effective to reduce the error.
| Translated title of the contribution | Error analysis and improvement of high voltage direct current power metering system |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 436-443 |
| Number of pages | 0 |
| Journal | 武汉大学学报:工学版 |
| Volume | 58 |
| Issue number | 3 |
| DOIs | |
| State | Published - 1 Mar 2025 |
Indexed by
- CSCD
Fingerprint
Dive into the research topics of 'Error analysis and improvement of high voltage direct current power metering system'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver