Abstract
In order to improve the performance of technology and economy for improvement of lightning protection, and reveal the failure cause of controllable discharging lightning rods and side needles, the incidence range of lightning current should be analyzed carefully. This paper proposed the calculation of whole-span lightning protection performance to simulate the status of the fault time, based on the lightning detection data, and the accurately topography and geomorphology data acquired by 3D geography information system (GIS). Through this simulation method, the fault property and the incidence range of lightning shielding failure current can be obtained. Moreover, the insulation configuration differences of adjacent towers and the protection range of lightning protection measures can be considered to verify the incidence range of lightning shielding failure current. This method has been verified by the typical fault in the mountain. In this example, the reason of lightning protection measure failure also has been explained quantitatively. The analysis result can be applied to the improvement of lightning protection.
| Translated title of the contribution | Analysis on the lightning trip-out failure of transmission line under conditions of complex landscape in a mountainous area |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 136-141 |
| Journal | Dianwang Jishu/Power System Technology |
| Volume | 35 |
| Issue number | 12 |
| State | Published - Dec 2011 |
Indexed by
- EI
Fingerprint
Dive into the research topics of 'Analysis on the lightning trip-out failure of transmission line under conditions of complex landscape in a mountainous area'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver