Skip to main navigation Skip to search Skip to main content

Breakdown Characteristics of a 220-kV Composite Insulator String Under Short Tail Lightning Impulses Based on the Discharge Current and Images

  • Xiangen Zhao*
  • , Gang Liu
  • , Lei Jia
  • , Hansheng Cai
  • , Bing Luo
  • , Yi Zhang
  • , Hongkun Chen
  • , Junjia He
  • *Corresponding author for this work
  • CSG
  • Huazhong Univ Sci & Technol

Research output: Contribution to journal › Article › peer-review

23 Scopus citations

Abstract

There are two hypotheses in the leader progression model to illustrate the insulator breakdown process. One is the streamer onset time is relatively small that can be ignored. The other is the leader velocity at both sides of the composite insulator strings are equal. These assumptions are mostly based on the experimental results in rod-rod air gaps. In this paper, experiments were performed to study the breakdown process of a 220-kV composite insulator string with grading rings under positive short tail lightning impulses. The discharge current at the high-voltage side and the high-speed photographs were recorded synchronously. The method of identifying four typical stages of the breakdown process from the current waveform was proposed. The experimental results show that the streamer onset time should not be ignored when calculating the breakdown time, especially for the composite insulator string with grading rings. By fitting the experimental results, the relationship between the streamer onset time and U-P / U-50 has been given. The results also indicate that the velocity of the positive leader is nearly 1.3 times than that of the negative leader during the breakdown process when the positive impulse is applied to the composite insulator string.
Original languageEnglish
Pages (from-to)3211-3217
Number of pages7
JournalIEEE Transactions on Power Delivery
Volume33
Issue number6
DOIs
StatePublished - Dec 2018

Funding

This work was supported by the Important Research Project in China Southern Power Grid under Grant KY2014-2-0015.

Keywords

  • Dielectric breakdown
  • composite insulation
  • lightning
  • current measurement
  • leader progression model

Indexed by

  • EI
  • Scopus
  • SCIE

Fingerprint

Dive into the research topics of 'Breakdown Characteristics of a 220-kV Composite Insulator String Under Short Tail Lightning Impulses Based on the Discharge Current and Images'. Together they form a unique fingerprint.