Abstract

Corrosion rate & grounding material selection is the key problem of substation grounding grid design. Corrosion current density of grounding materials calculated from electrochemical polarization curve experiment can be used to select material and evaluate the corrosion rate in grounding grid of electrical engineering. Low-polarization curves of carbon steel, galvanized steel and copper in three different saturated soil samples were measured by a three-electrode system & electrochemical workstation first. Then the fitting effects of measured polarization curves using analyzed results of the four basic algorithms, including Barnartt three-point method, Single-polarization three-point method, Jankowski & Juchniwi four-point method and Combination of linear-polarization and low-polarization method, were analyzed and compared in detail. Results show that, the basic algorithms mentioned above have defects such as data utilization rate is low, or there may be no results to be obtained because the radicand is less than zero during data processing, or fitting effects are poor. Then Levenberg-Marquardt curve-fitting algorithm is introduced to deal with low-polarization curves of grounding grid materials, which is proved to be able to avoid limitations of the basic algorithms. Levenberg-Marquardt curve-fitting algorithm is a new effective measure to evaluate the corrosion rate of grounding grid materials in the laboratory. © 2012 Chin. Soc. for Elec. Eng.
Translated title of the contributionCorrosion rate evaluation for grounding grid material by low-polarization curve method
Original languageChinese
Pages (from-to)192-198
Number of pages7
JournalZhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
Volume32
Issue number28
StatePublished - Jan 2012

Indexed by

  • Scopus

Fingerprint

Dive into the research topics of 'Corrosion rate evaluation for grounding grid material by low-polarization curve method'. Together they form a unique fingerprint.

Cite this