Skip to main navigation Skip to search Skip to main content

Design of variable frequency dielectric loss meter based on C8051F040 MCU

Translated title of the contribution: Design of variable frequency dielectric loss meter based on C8051F040 MCU
  • Li Ming-Dong
  • , Li Wen-An
  • , Ren Bo
  • , Wang Ying-Chun
  • , Wang Ya-Jun

Research output: Contribution to journal › Article › peer-review

Abstract

Based on the analysis of conventional and modern dielectric loss measurement methods, the variable frequency measurement of dielectric loss is an effective method to suppress the interference of strong electric field of power grid on site. By setting the frequency of test voltage far away from 50 Hz, the interference of power frequency becomes bias-frequency interference. Applying Fourier transform frequency spectrum analysis, the equivalent formula and arithmetic for calculating the dielectric loss at power frequency are deduced. With MAX197 and C8051F040 as cores of data acquisition and control processing, the system hardware design and principle of data processing are expounded.
Translated title of the contributionDesign of variable frequency dielectric loss meter based on C8051F040 MCU
Original languageChinese
Pages (from-to)51-53
Number of pages3
JournalDianli Zidonghua Shebei/Electric Power Automation Equipment
Volume26
Issue number9
StatePublished - Jan 2006

Indexed by

  • Scopus

Fingerprint

Dive into the research topics of 'Design of variable frequency dielectric loss meter based on C8051F040 MCU'. Together they form a unique fingerprint.

Cite this