Abstract
Based on the analysis of conventional and modern dielectric loss measurement methods, the variable frequency measurement of dielectric loss is an effective method to suppress the interference of strong electric field of power grid on site. By setting the frequency of test voltage far away from 50 Hz, the interference of power frequency becomes bias-frequency interference. Applying Fourier transform frequency spectrum analysis, the equivalent formula and arithmetic for calculating the dielectric loss at power frequency are deduced. With MAX197 and C8051F040 as cores of data acquisition and control processing, the system hardware design and principle of data processing are expounded.
| Translated title of the contribution | Design of variable frequency dielectric loss meter based on C8051F040 MCU |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 51-53 |
| Number of pages | 3 |
| Journal | Dianli Zidonghua Shebei/Electric Power Automation Equipment |
| Volume | 26 |
| Issue number | 9 |
| State | Published - Jan 2006 |