Abstract
The audible noise (AN) induced by corona discharge of AC transmission lines is more severe at high altitudes than at low altitudes; this has become a crucial limiting factor for the structural design of power lines and their environmental impact assessment. To determine the altitude effect and correction of AN level for AC power lines, a corona cage test system was used to measure the acoustic power level of four bundled conductors at five elevations, namely Wuhan (23 m), Tianshui (1100 m), Xining (2261 m), Gonghe (2943 m), and Yangbajain (4300 m). We obtained the AN characteristics for different altitudes, bundle numbers, and subconductor diameters through a statistical analysis of measured data. The analysis and comparison results indicate that the actual AN correction values are slightly less than the Bonneville Power Administration term of 1 dB/300 m at altitudes below 3200 m. Above 3200 m, the difference increases gradually. A correction term 2.85 dB/1000 m is recommended for more accurate evaluation.
| Original language | English |
|---|---|
| Article number | 1055 |
| Number of pages | 10 |
| Journal | ENERGIES |
| Volume | 10 |
| Issue number | 7 |
| DOIs | |
| State | Published - Jul 2017 |
Funding
This work was supported by State Key Laboratory of Power Grid Environmental Protection and the State Grid Corporation of China (SGCC) Science and Technology Project of China under Grant GY71-17-005, which supplied the costs of publishing in open access. The authors would also particularly like to thank Yulong Chen and Huagang Liu (China Electric Power Research Institute, China) for their consistent support throughout the experiment procedure.
Keywords
- ultra-high voltage AC power lines
- corona performance
- audible noise
- high altitude correction
Indexed by
- EI
- Scopus
- SCIE
Fingerprint
Dive into the research topics of 'Effect of Altitude on the Audible Noise Level of AC Power lines'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver