Skip to main navigation Skip to search Skip to main content

Experimental Research on V-t Characteristics of C5F10O/CO2 Gas Mixture Under Lighting Impulse Voltage

  • Guangdong Power Grid Corp
  • State Grid Chongqing Elect Power Res Inst

Research output: Contribution to journal › Article › peer-review

5 Scopus citations

Abstract

C5F10O has excellent insulation and environmental performance. It has the potential to replace SF(6 )in low-and medium-voltage gas-insulated equipment. For gas-insulating medium, its breakdown law under the impulse voltage is an important basis for the design and calibration of equipment insulation. The research on the insulation performance of C(5)F(10)Omixed gas under the impulse voltage is still incomplete. In this article, the empirical formula of the V-t characteristic curve of C5F10O/CO2 mixed gas is obtained through the lightning impulse withstand voltage test under extremely nonuniform electric field, and compared with the SF6 under the same conditions. The results showed that the breakdown voltage of C5F10O/CO2 and SF6 decreases with the increase of breakdown time and stabilizes at around U50% with the extension of breakdown time. The breakdown point ofC(5)F(10)O/CO2 mixed gas shows a significant "peak accumulation" effect. As the pressure increases, the V-t curve will rise accordingly, the distribution of breakdown points will become more compact, and the steepness of the curve will be steeper. In addition, the increase of C5F10O content and the change of the gap distance will also shorten the discharge time delay, so that the distribution of the breakdown point is more concentrated, and the steepness of the V-t characteristic curve becomes larger. In particular, the V-t characteristic curve of C5F10O/CO2 gas mixture appears to increase with the increases of breakdown time when the gas distance is small due to the influence of space charge layer, and this phenomenon changes when the distance increases. The results provide an important basis for the insulation design and calibration of C5F10O mixed-gas insulated equipment.
Original languageEnglish
Pages (from-to)2134-2141
Number of pages8
JournalIEEE Transactions on Dielectrics and Electrical Insulation
Volume30
Issue number5
Early online dateJan 2023
DOIs
StatePublished - Oct 2023

Funding

This work was supported in part by the National Natural Science Foundation of China under Grant 51877157 and Grant 52277161, and in part by the Hubei Province Science Fund for Distinguished Young Scholars under Grant 2020CFA097.

Keywords

  • C5F10O gas mixture
  • lightning impulse breakdown characteristics
  • SF6 alternative gas
  • V-t characteristic

Indexed by

  • Scopus
  • EI
  • SCIE

Fingerprint

Dive into the research topics of 'Experimental Research on V-t Characteristics of C5F10O/CO2 Gas Mixture Under Lighting Impulse Voltage'. Together they form a unique fingerprint.

Cite this