Abstract
Similar to transmission line grounding system, grounding system for GIL transmission also plays an important role in stable and reliable operation. In this paper, the grounding system of GIL is studied. Firstly, a grounding system model of GIL is established, and earthing resistance, step voltage, touch voltage and earth potential rise are calculated and analyzed in this model. And then, some influencing factors of GIL grounding system are studied, such as concrete structure reinforcement, the uniformity and un-uniformity layout of terminal grounding grid, the cross connection distance of tinned copper, and the cross connection distance of the main structure steel connecting tinned copper. Finally, the influence rules of sensitive factors impacting grounding system are obtained. In design stage of GIL grounding system, it is necessary to give priority to connecting concrete structural reinforcement and copper line of grounding as natural grounding body, and the connection distance of grounded copper bars is the least influencing factor. The reasonable design parameters of grounding system from the perspective of electrical model are suggested, providing basis for construction and operation of integrated GIL corridor.
| Translated title of the contribution | Influence of GIL Tube Structure Parameters on Electrical Characteristics of Grounding System |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 3032-3038 |
| Number of pages | 7 |
| Journal | Dianwang Jishu/Power System Technology |
| Volume | 43 |
| Issue number | 8 |
| Early online date | 19 Oct 2018 |
| DOIs | |
| State | Published - Jan 2019 |
Funding
国家自然科学基金项目(51777037);国家电网公司科技指南项目(524625180018)~~;
Indexed by
- EI
- Scopus
- CSCD
Fingerprint
Dive into the research topics of 'Influence of GIL Tube Structure Parameters on Electrical Characteristics of Grounding System'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver