Skip to main navigation Skip to search Skip to main content

GIS中盆式绝缘子沿面放电的新特征气体CS2

Translated title of the contribution: Creeping Discharge Monitoring of Epoxy Spacers in GIS Using a New Target Gas CS_2
  • 广东电网公司电力科学研究院

Research output: Contribution to journal › Article › peer-review

34 Scopus citations

Abstract

Creeping discharge on the epoxy spacer is a major kind of fault in gas insulated switchgear(GIS). It is important to monitor the insulation condition of epoxy spacers and to study the variations of target gases when partial discharges occur on the epoxy spacer in GIS. A new decomposed gas CS2 is found in the simulation experiments by current researchers. It is detected when creeping discharges occur on the surface of epoxy spacer, and is validated by experiment on a small apparatus and 110 k V GIS. B3P86, a method of calculation based on quantum chemistry, is adopted to explore the formation of the CS2 and energy conditions. Experiments and theoretical calculations show that complex chemical reactions happen when creeping discharges occur on the epoxy spacer in GIS, and CS2 is generated through various ways. Carbon is the component of CS2 derived from the charring epoxy spacer. As an effective target gas, CS2 can be applied to diagnose faults related to creeping discharge on the epoxy spacer in GIS. Many latent faults leading to creeping discharge on the epoxy spacer have been diagnosed using target gas CS2 in actual production.
Translated title of the contributionCreeping Discharge Monitoring of Epoxy Spacers in GIS Using a New Target Gas CS_2
Original languageChinese
Pages (from-to)848-856
Number of pages9
JournalGaodianya Jishu/High Voltage Engineering
Volume41
Issue number3
DOIs
StatePublished - 31 Mar 2015

Indexed by

  • Scopus
  • CSCD

Fingerprint

Dive into the research topics of 'Creeping Discharge Monitoring of Epoxy Spacers in GIS Using a New Target Gas CS_2'. Together they form a unique fingerprint.

Cite this