Abstract

A harmonic analysis method based on ANF (Adaptive Notch Filter) is proposed to improve the interference suppression of dielectric loss angle measurement. ANF can effectively filter out the integer harmonics, inter-harmonics and noise contained in the voltage/current waveform, track the fundamental component and accurately extract the fundamental frequency, with which, the dielectric loss angle is calculated by harmonic analysis method. Simulative result indicates that, the method of harmonic analysis based on ANF has higher measurement precision in the conditions of frequency fluctuation, harmonic component variation, white noise, dielectric loss angle variation, initial phase angel variation and so on.
Translated title of the contributionHarmonic analysis based on ANF
Original languageChinese
Pages (from-to)100-104
Number of pages5
JournalDianli Zidonghua Shebei/Electric Power Automation Equipment
Volume33
Issue number9
DOIs
StatePublished - Sep 2013