As a classical theory for solving the statistic problems, the Markov model has been rarely used in the field of power engineering, especially in the prediction of operation conditions and quantitative calculation for failure probability of transmission lines (insulators), where pollution flashover and other failures may occur. We established a state assessment model of transmission lines (insulators) on the basis of the Markov process, including the Markov process state transition diagrams and Markov process matrix. The 500 kV transmission lines' empirical operation data of Hubei Province from 2001 to 2005 were used to compute the failure rate λk and repair rate μk as an example. Failure rate λk and repair rate μk are imported into the Markov model matrix equation to compute the reliability of transmission lines and a variety probability pi of unavailable or failure state in Hubei Province. Using the established assessment model, we can calculate the whole state reliability parameters of 500 kV transmission lines, the average available time t¯fs and mean repair time t¯rs in Hubei Province from 2001 to 2005.
| Translated title of the contribution | Operating risk assessment for transmission and line insulators using Markov model |
|---|---|
| Original language | Chinese |
| Pages (from-to) | 1952-1960 |
| Journal | Gaodianya Jishu/High Voltage Engineering |
| Volume | 37 |
| Issue number | 8 |
| State | Published - Aug 2011 |