T1 - Reactive Power Configuration Scheme for Receiving-End Power Grids Based on Multi-Objective Particle Swarm Optimization
AU - Huang, Ying
AU - Liu, Xuecheng
AU - Wu, Yajun
AU - Pan, Xiaojie
AU - Shao, Dejun
AU - Shi, Mengxuan
AU - Zhang, Mujie
AU - Yang, Jun
PY - 2026/1
Y1 - 2026/1
N2 - Receiving-end power grids are usually characterized by dense loads, high reactive power demand, and weak voltage support. Fluctuations in daily load profiles and renewable energy generation may lead to increased voltage deviation and active power losses. To achieve a comprehensive optimization of reactive power resources considering economy, security, and engineering feasibility, this paper proposes a reactive power configuration scheme based on multi-objective particle swarm optimization (MOPSO). Taking the IEEE 30-bus system as a test case, an AC power flow model under a 24-hour typical operating scenario is established. Subject to power flow equality constraints, bus voltage limits, and equipment operating boundaries, three objectives are simultaneously minimized: daily accumulated active power loss, daily average voltage deviation, and investment cost of reactive power compensation devices. The model explicitly incorporates the capacity configuration variables of static var compensators (SVCs), shunt capacitor banks, and energy storage systems, and further considers practical constraints such as capacitor switching frequency. A uniformly distributed Pareto-optimal solution set is obtained using an external archive and grid-based crowding control mechanism. Simulation results demonstrate that the proposed method provides a clear trade-off between loss reduction and voltage quality improvement, while offering intuitive guidance for reactive power device operation and configuration, thereby supporting decision-making for reactive power planning and operation in receiving-end power grids. © 2026 IEEE.
AB - Receiving-end power grids are usually characterized by dense loads, high reactive power demand, and weak voltage support. Fluctuations in daily load profiles and renewable energy generation may lead to increased voltage deviation and active power losses. To achieve a comprehensive optimization of reactive power resources considering economy, security, and engineering feasibility, this paper proposes a reactive power configuration scheme based on multi-objective particle swarm optimization (MOPSO). Taking the IEEE 30-bus system as a test case, an AC power flow model under a 24-hour typical operating scenario is established. Subject to power flow equality constraints, bus voltage limits, and equipment operating boundaries, three objectives are simultaneously minimized: daily accumulated active power loss, daily average voltage deviation, and investment cost of reactive power compensation devices. The model explicitly incorporates the capacity configuration variables of static var compensators (SVCs), shunt capacitor banks, and energy storage systems, and further considers practical constraints such as capacitor switching frequency. A uniformly distributed Pareto-optimal solution set is obtained using an external archive and grid-based crowding control mechanism. Simulation results demonstrate that the proposed method provides a clear trade-off between loss reduction and voltage quality improvement, while offering intuitive guidance for reactive power device operation and configuration, thereby supporting decision-making for reactive power planning and operation in receiving-end power grids. © 2026 IEEE.
KW - Costs
KW - Economics
KW - Electric load flow
KW - Electric power transmission networks
KW - Investments
KW - Multiobjective optimization
KW - Pareto principle
KW - Reactive power
KW - Renewable energy
KW - Static Var compensators
KW - Value engineering
KW - Grid-based
KW - Multi objective particle swarm optimization
KW - Multi-objectives optimization
KW - Particle swarm
KW - Particle swarm optimization
KW - Power grids
KW - Reactive power configurations
KW - Receiving-end power grid
KW - Swarm optimization
KW - Voltage deviations
KW - Economic and social effects
KW - Particle swarm optimization (PSO)
KW - multi-objective optimization
KW - particle swarm optimization
KW - reactive power configuration
KW - receiving-end power grid
KW - voltage deviation
UR - https://openir.whu.edu.cn/AchievementDetail/EI_6525fcc6-3104-4854-8c0a-9c136bd92b75
U2 - 10.1109/iceaai68945.2026.11442567
DO - 10.1109/iceaai68945.2026.11442567
M3 - Conference contribution
SN - 979-833157148-1
T3 - Int. Conf. Electr. Autom. Artif. Intell., ICEAAI
SP - 133
EP - 136
BT - 2026 2nd International Conference on Electrical Automation and Artificial Intelligence, ICEAAI 2026
PB - Institute of Electrical and Electronics Engineers Inc.
ER -