Skip to main navigation Skip to search Skip to main content

Research on Conducted Disturbance to Secondary Cable Caused by Disconnector Switching Operation

  • Xiaoyue Chen*
  • , Zeyu He
  • , Yanze Zhang
  • , Junjie Si
  • , Shuang Wang
  • , Baoquan Wan
  • , Jianben Liu
  • *Corresponding author for this work
  • State Grid Shaoxing Power Supply Co
  • State Key Lab Power Grid Environm Protect

Research output: Contribution to journal › Article › peer-review

5 Scopus citations

Abstract

The disconnector switching operation in GIS not only generates very fast transient overvoltage (VFTO) in primary equipment, but also couples to the secondary system, which affects normal operation of the secondary equipment. In this study, aiming at the conducted disturbance caused by the disconnector switching operation of the 1,000-kV UHV GIS test circuit on the secondary cable, a broadband equivalent circuit model of the potential transformer and the grounding grid is proposed based on the vector fitting method and the impedance synthesis method, and the accuracy of the model is tested. On the basis of this model, the conducted disturbance voltage of the secondary cable core is obtained by combining the measured typical disturbance source waveform. The research results of the influencing factors of conducted disturbance show that the amplitude of the disturbance voltage generated by the capacitive conduction is higher than that generated by the resistive conduction, but the main frequency of the resistive conducted disturbance voltage is higher. The amplitude of the conducted disturbance voltage will decrease with the increase of the length of the cable and the length of the grounding wire. The single-ended grounding of the secondary cable shield at the GIS side will cause serious disturbance voltage. The research results of this study will be beneficial to the protection of secondary cable electromagnetic disturbance in the intelligent substation and have reference significance for the implementation of secondary equipment protection measures in the intelligent substation.
Original languageEnglish
Article number819021
Number of pages11
JournalFRONTIERS IN ENERGY RESEARCH
Volume9
DOIs
StatePublished - 7 Jan 2022

Funding

Funding This research was funded by Open Fund of State Key Laboratory of Power Grid Environment Protection (No. GYW51202001551).

Keywords

  • disconnector switching operation
  • broadband equivalent circuit model
  • finite integral method
  • overall electromagnetic disturbance
  • suppression measures