Setting of zero-sequence current compensation coefficient for ground distance relays of double-circuit transmission lines on same tower considering capacitive current

Translated title of the contribution: Setting of zero-sequence current compensation coefficient for ground distance relays of double-circuit transmission lines on same tower considering capacitive current
  • Wei Li
  • , Jian Chen
  • , Meiling Jiang
  • , Zhijian Hu
  • , Xiaomin Cheng
  • Hunan Electric Power Dispatch and Communication Bureau
  • Hunan Electric Power Corporation Research Institute

Research output: Contribution to journal › Article › peer-review

Abstract

The influences of zero-sequence mutual inductance between the two circuits and capacitive current on zero-sequence current compensation coefficient were analyzed while the two circuits of double circuit transmission lines on the same tower are operated independently. A mathematical model of ground distance protection was derived, and based on traditional ground distance protection a new method to set zero-sequence current compensation coefficient was proposed, i.e., the zero-sequence current compensation coefficient was regarded as the sum of original zero-sequence current compensation coefficient, additional zero-sequence current compensation coefficient and additional capacitive current compensation coefficient, meanwhile the computing formulae of the three zero-sequence current compensation coefficients were given. Results of PSCAD-based simulation showed that when the setting range was eighty percent of total length of the transmission line and the fault occurred at the end of the transmission line, the fault position could be reflected by the proposed method more precisely than by traditional methods, besides, the first zones within the protection regions measured from both ends of the transmission line could be overlapped, thus the performance of ground distance protection for double-circuit transmission lines on the same tower could be improved.
Translated title of the contributionSetting of zero-sequence current compensation coefficient for ground distance relays of double-circuit transmission lines on same tower considering capacitive current
Original languageChinese
Pages (from-to)281-284
JournalDianwang Jishu/Power System Technology
Volume36
Issue number7
StatePublished - Jul 2012