Skip to main navigation Skip to search Skip to main content

Study on static and dynamic voltage distribution characteristics of modularized multi-break vacuum circuit breaker with series and parallel configuration

Translated title of the contribution: Study on static and dynamic voltage distribution characteristics of modularized multi-break vacuum circuit breaker with series and parallel configuration

Research output: Contribution to journal › Article › peer-review

19 Scopus citations

Abstract

To offer the reference for the design of static and dynamic insulation characteristics of multi-break vacuum circuit breaker (VCB) with fiber-controlled vacuum circuit modules, three-dimensional finite element analysis models are built to calculate the static potential distribution of 126 kV triple-break VCB with U-shaped arrangement and the electric field distribution within its interior vacuum interrupters. By use of 110 kV oscillatory synthetic test circuit, the low-voltage and small-current breaking tests of the modularized triple-break prototype of VCB connected in series are performed and the distribution of the transient recovery voltage (TRV) of the three breaks are measured. Results of calculation and tests show that the static and dynamic voltage distributions of triple-break VCB are uneven under U-shaped arrangement, more than 65% of static voltage is divided to the break at high voltage side, and during this test it is not necessary to install the support under the bottom of the tested prototypes connected in series; more than 60% of dynamic voltage, i. e., the peak of TRV, is divided to the break at high voltage side while the grading capacitor with capacitance of 1000 pF can meet the requirement of voltage sharing of the breaking under low-voltage and small-current, however the breaking under high-voltage and large-current should be further verified.
Translated title of the contributionStudy on static and dynamic voltage distribution characteristics of modularized multi-break vacuum circuit breaker with series and parallel configuration
Original languageChinese
Pages (from-to)181-186
Number of pages6
JournalDianwang Jishu/Power System Technology
Volume35
Issue number7
StatePublished - Jan 2011

Indexed by

  • Scopus

Fingerprint

Dive into the research topics of 'Study on static and dynamic voltage distribution characteristics of modularized multi-break vacuum circuit breaker with series and parallel configuration'. Together they form a unique fingerprint.