Skip to main navigation Skip to search Skip to main content

The Method for On-Line Monitoring of tanδ of Transformer Bushing Based on Conductor Temperature Distribution

  • Zhifei Yang
  • , Jiangjun Ruan
  • , Zhiye Du*
  • , Zhibin Qiu
  • , Taotao Zhou
  • , Liezheng Tang
  • , Bihui Zhang
  • *Corresponding author for this work

Research output: Contribution to journal › Article › peer-review

Abstract

On-line monitoring of dielectric loss factor of transformer bushing is of great significance to its safe and stable operation. However, on-line monitoring has problems of large disturbance and potential safety concerns. In this paper, a new method for on-line monitoring of dielectric loss factor of transformer bushing is proposed to overcome these problems. Optical fiber temperature measurement system is placed inside the conductor. According to relationship between the dielectric loss factor (tans) and conductor temperature distribution, the tans can be obtained by using finite element multi-physical field coupling method. This method is verified by the example of a 220 kV transformer bushing, and the error is less than 8%. This method is used to overcome the existing problems in on-line monitoring of dielectric loss factor.
Original languageEnglish
Pages (from-to)1168-1176
Number of pages9
JournalJOURNAL OF NANOELECTRONICS AND OPTOELECTRONICS
Volume14
Issue number8
DOIs
StatePublished - Aug 2019

Funding

This research is supported by National Natural Science Foundation of China (51477120) and (51741708).

Keywords

  • Transformer Bushing
  • Temperature Field Distribution
  • On-Line Monitoring
  • Dielectric Loss Factor

Indexed by

  • SCIE

Fingerprint

Dive into the research topics of 'The Method for On-Line Monitoring of tanδ of Transformer Bushing Based on Conductor Temperature Distribution'. Together they form a unique fingerprint.

Cite this