AC Breakdown Characteristics of Overhead Transmission Line Phase Conductor-Ground Air Gap Under Wildfire Condition

  • Daochun Huang*
  • , Shuolun Zhou
  • , Huaqing Wang
  • , Enze Zhou
  • , Tianhao Peng
  • *此作品的通讯作者
  • China Southern Power Grid Technology Co.
  • Electric Power Research Institute of Guangdong Power Grid Co.

科研成果: 期刊稿件 › 论文 › 同行评审

摘要

Wildfires may cause overhead transmission lines to trip, jeopardizing the safe and stable operation of the power grid. In order to provide support for the risk assessment of overhead transmission lines phase conductor-ground air gap short circuit breakdown under wildfire condition, the conductor-ground 1.2-9m air gap AC breakdown tests under vegetation fire condition are carried out. The influence of five factors—vegetation type, vegetation moisture content, number of sub-conductors in a bundle, gap distance, and altitude—on breakdown characteristics are investigated. The results show that using fir as a reference, the correction coefficients for the average breakdown voltage gradients of pine, eucalyptus, shrub, and thatch are 1.13, 0.96, 0.93, and 0.88 respectively. The average breakdown voltage gradient in the flame zone is significantly affected by vegetation moisture content. Under typical dense smoke conditions, smoke reduces gap insulation effectiveness by approximately 16%. As the gap distance increases, the gap discharge process remains stable, but the arcing phenomenon becomes increasingly pronounced. The arc colors in the smoke zone and flame zone are distinctly differentiated. Number of sub-conductors in a bundle has negligible effect on gap insulation strength. As the gap distance increases, the insulation strength in the flame zone remains stable, but the average breakdown voltage gradient across the gap gradually increases, making the gap more difficult to breakdown. With increasing altitude, the insulation strength of the continuous flame zone is minimally affected, while the insulation strength of the discontinuous flame zone and vegetation burn intensity exhibit a certain degree of decline. © 1994-2012 IEEE.
源语言英语
期刊IEEE Transactions on Dielectrics and Electrical Insulation
DOI
出版状态刊载前的电子出版物 - 1月 2026

基金资助

National Natural Science Foundation of China, Number: GDKJXM20222564, Acronym: CSG, China Southern Power Grid (NNSF) [51677138];

关键词

  • AC breakdown characteristics
  • gap breakdown test
  • overhead transmission line
  • phase conductor-ground air gap
  • wildfire