跳到主要导航 跳到搜索 跳到主要内容

Breakdown Characteristics of a 220-kV Composite Insulator String Under Short Tail Lightning Impulses Based on the Discharge Current and Images

  • Xiangen Zhao*
  • , Gang Liu
  • , Lei Jia
  • , Hansheng Cai
  • , Bing Luo
  • , Yi Zhang
  • , Hongkun Chen
  • , Junjia He
  • *此作品的通讯作者
  • CSG
  • Huazhong Univ Sci & Technol

科研成果: 期刊稿件 › 论文 › 同行评审

23 引用 (Scopus)

摘要

There are two hypotheses in the leader progression model to illustrate the insulator breakdown process. One is the streamer onset time is relatively small that can be ignored. The other is the leader velocity at both sides of the composite insulator strings are equal. These assumptions are mostly based on the experimental results in rod-rod air gaps. In this paper, experiments were performed to study the breakdown process of a 220-kV composite insulator string with grading rings under positive short tail lightning impulses. The discharge current at the high-voltage side and the high-speed photographs were recorded synchronously. The method of identifying four typical stages of the breakdown process from the current waveform was proposed. The experimental results show that the streamer onset time should not be ignored when calculating the breakdown time, especially for the composite insulator string with grading rings. By fitting the experimental results, the relationship between the streamer onset time and U-P / U-50 has been given. The results also indicate that the velocity of the positive leader is nearly 1.3 times than that of the negative leader during the breakdown process when the positive impulse is applied to the composite insulator string.
源语言英语
页(从-至)3211-3217
页数7
期刊IEEE Transactions on Power Delivery
卷33
期6
DOI
出版状态已出版 - 12月 2018

基金资助

This work was supported by the Important Research Project in China Southern Power Grid under Grant KY2014-2-0015.

关键词

  • Dielectric breakdown
  • composite insulation
  • lightning
  • current measurement
  • leader progression model

收录

  • EI
  • Scopus
  • SCIE

学术指纹

探究 'Breakdown Characteristics of a 220-kV Composite Insulator String Under Short Tail Lightning Impulses Based on the Discharge Current and Images' 的科研主题。它们共同构成独一无二的学术指纹。

引用此