跳到主要导航 跳到搜索 跳到主要内容

DC magnetic bias induced current effects on transformer and restricting methods

  • Xi'an Power Supply Bureau

科研成果: 期刊稿件 › 论文 › 同行评审

36 引用 (Scopus)

摘要

This paper proposes a study of the influence of the HVDC (High Voltage Direct Current transmission) ground electrode current on neutral grounding transformer. According to the ferromagnetic hysteresis theory established by Jiles-Atherton, a new transformer model has been built At the same time the model is applied in the simulation of direct current magnetic bias on transformer. The simulation results commendably reflect the disadvantageous influence on the transformer, which caused by the distortion of the waveform and the amplitude of the exciting current. On the basis of these researches, solutions of restricting transformer direct-current magnetic bias, such as installing a bypassing device in parallel with the capacitor installed in the neutral and so on are introduced. The problems caused by the direct current magnetic bias, e. g. transformer's copper loss, iron loss and noise increment, can be analyzed and solved by adopting the model and methods mentioned above. The application of the proposed algorithm to a test system shows its validity.
投稿的翻译标题DC magnetic bias induced current effects on transformer and restricting methods
源语言中文
页(从-至)117-120
页数4
期刊Gaodianya Jishu/High Voltage Engineering
卷32
期9
出版状态已出版 - 1月 2006

关键词

  • Direct-current magnetic bias
  • Ferromagnetic hysteresis
  • Ground electrode
  • HVDC
  • Transformer