跳到主要导航 跳到搜索 跳到主要内容

Erosion-corrosion behavior of aluminum in a 50°C ethylene glycol aqueous solution simulating cooling water in HVDC transmission

  • Yingfu Tian
  • , Huixi Li
  • , Shengping Wang*
  • , Youping Fan*
  • *此作品的通讯作者
  • Tianshengyiao Bur
  • China Univ Geosci

科研成果: 期刊稿件 › 论文 › 同行评审

13 引用 (Scopus)

摘要

The erosion-corrosion of aluminum in a 50 degrees C ethylene glycol aqueous solution (EGAS) was studied. Compared with that in deionized water, the corrosion of aluminum in an EGAS was inhibited to a certain extent. The corrosion potential, corrosion current, and charge transfer impedance of aluminum changed from -1.5776 V, 380.4 nA cm(-2), and 1.924 x 10(-4) omega cm(-2) in deionized water to -1.3127 V, 285.5 nA cm(-2), and 4.041 x 10(-4) omega cm(-2) in a 45.3 vt% EGAS, respectively. Ethylene glycol did not ionize in deionized water and the ionic conductivity of the EGAS was low, effectively restraining the corrosion of aluminum. However, a test with aluminum in an EGAS after long-term storage (9 days) showed that ethylene glycol gradually oxidized to glycolic acid, oxalic acid, and other substances, which slowly corroded the aluminum surface. Analysis results showed that the corrosion products on the surface of aluminum were Al(OH)(3) and Al2O3. The pitting hole formation mechanism of aluminum occurs via an aluminum-alcohol phase formed on the aluminum surface, which can inhibit the dissolution of the oxide film. Therefore, a suitably concentrated EGAS with a high heat capacity and low ionic conductivity similar to that of deionized water can be used as a coolant in airtight valve cooling systems for high-voltage direct-current transmission.
源语言英语
页(从-至)1899-1907
页数9
期刊Materials and Corrosion
卷72
期12
早期在线日期8月 2021
DOI
出版状态已出版 - 12月 2021

基金资助

Programs of the China Southern Power Grid, Grant/Award Numbers: CGYKJXM20180229, 20180405

关键词

  • aluminum
  • erosion-corrosion
  • ethylene glycol
  • high-voltage direct-current transmission
  • radiator

收录

  • EI
  • Scopus
  • SCIE

学术指纹

探究 'Erosion-corrosion behavior of aluminum in a 50°C ethylene glycol aqueous solution simulating cooling water in HVDC transmission' 的科研主题。它们共同构成独一无二的学术指纹。