Fouling occurred on heat exchangers in a Chinese power plant. The investigation included composition analysis and comparisons of cooling water, fouling, silt, microorganisms, and biological slime. Silt was found to be the source of the fouling. Results indicate that silt should be considered in the daily water quality monitoring process in a direct drainage-type cooling water system. The cooling water intake should be kept high enough above the supply reservoir bottom to prevent picking up silt.