This paper provides an effective misalignment fault diagnosis method of the gas-insulated switchgear (GIS) disconnector. Relationships between contact forces and the surrounding magnetic field in various mechanical assembly conditions were studied by the 3-D electromagnetic-mechanical coupled finite-element model and physical experiments. First, spring deformation and contact forces on individual contact elements were obtained bymechanical field analysis. Holding springs weremodeled by equivalent elastic rings during analysis. Second, themagnetic field around the GIS disconnector was obtained by electromagnetic-field analysis. Contact resistances on contact interfaces weremodeled by cylindrical bridges, which use mechanical contact forces as parameter inputs. Physical tests have been carried on the prototype GIS disconnector with various artificial misalignment faults. In different situations of misalignment faults under ac current, surrounding magnetic flux densities were measured by the Hall sensor array. Calculated and measured results have the same trend that the mechanical misalignment fault could change distributions of contact forces then make distortion of currents and the surrounding magnetic field. Magnetic-field behaviors of the GIS disconnector with differentmechanical assembly conditions were studied. The results show that the deviation of magnetic flux density becomes larger while reducing holding spring stiffness, decreasing movable conductor insert depth, and increasing the movable conductor docking angle.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 2484-2491 |
| 页数 | 8 |
| 期刊 | IEEE Transactions on Power Delivery |
| 卷 | 33 |
| 期 | 5 |
| DOI | |
| 出版状态 | 已出版 - 10月 2018 |
基金资助
This work was supported in part by the Natural Science Foundation of China (51607124), in part by the Fundamental Research Funds for China Central Universities (2042016kf1049, 2017kfy011), and in part by the 60th China Postdoctoral Science Foundation (2016M602352).
关键词
- Contact status
- disconnector
- fault diagnosis
- finite element method
- gas insulated switchgear
- magnetic field
收录
- EI
- Scopus
- SCIE
学术指纹
探究 'Finite Element Analysis on Forces, Currents, and Magnetic Fluxes of Misaligned GIS Disconnector' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver