摘要
In the presented power system analysis software, the actuator model of hydro turbine governor system cannot effectively reflect the actual characteristics of the section closing law. The accuracy of Francis turbine model simulation is not high since the Francis turbine static characteristic curve between turbine power and guide vane opening is obviously nonlinear under a certain water head. An improved actuator model was proposed with section closing rate limits, which reflects the section closing law of the guide vane. The simulation analysis shows that the section closing point has a great effect on the Francis turbine in case of load rejection when the vane is fully closed. Compared with different fitting methods of the mechanical power and guide vane opening, the cubic polynomial fitting method is more suitable and recommended. An improved nonlinear turbine model with nonlinear characteristics of mechanical power versus gate position was established. The comparison between the simulation and field test data demonstrates that the improved nonlinear Francis turbine-governor model considering section closing law of guide vane is more practical and effective than the existing models, thus can be better applied in power system simulation analysis.
| 源语言 | 英语 |
|---|---|
| 期刊论文编号 | e2525 |
| 页数 | 14 |
| 期刊 | INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS |
| 卷 | 28 |
| 期 | 5 |
| DOI | |
| 出版状态 | 已出版 - 5月 2018 |
基金资助
National Natural Science Foundation of China, Grant/Award Numbers: 51307123 and 51677137
关键词
- curve fitting
- Francis turbine
- governor
- section closing law
- turbine mechanical power and guide vane opening
收录
- EI
- Scopus
- SCIE
学术指纹
探究 'Improved nonlinear turbine-governor model and parameter assessment for a large hydropower plant' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver