Mechanical fault diagnosis of outdoor high-voltage disconnector

科研成果: 期刊稿件 › 论文 › 同行评审

25 引用 (Scopus)

摘要

A series of experiments are conducted on a 252-kV pantograph disconnector offline to monitor its mechanical condition. Three parameters, namely the dynamic strain of the post insulator, the rotation angle of the operating shaft, and the stator current of the driving motor, are measured by resistance strain gauges, magnetic-sensing angle transducer, and Hall current sensor, respectively. Measurement results of the three parameters under mechanical fault conditions including clamping stagnation of the conduct tube knuckle, failure of the balance spring, and uncompleted closing operation are compared with those in normal operating condition of the disconnector. The results indicate that the dynamic strain waveform, the rotation angle curve, and the motor current envelope waveform may get distorted with increased peak value and offset peak time when mechanical faults happen to the transmission or rotating mechanism of the disconnector, and more component of the side frequency will appear in the spectrum of the motor current waveform. The proposed methods are validated to be effective for mechanical fault diagnosis and condition assessment of pantograph disconnector, and are also of reference significance for other types of disconnectors. (c) 2016 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
源语言英语
页(从-至)556-563
页数8
期刊IEEJ Transactions on Electrical and Electronic Engineering
卷11
期5
DOI
出版状态已出版 - 9月 2016

基金资助

The authors wish to thank the Fundamental Research Funds for Central Universities in China (Grant No. 201420720201) for financially supporting this study.

关键词

  • high-voltage disconnector
  • mechanical fault
  • motor current
  • strain
  • rotation angle
  • clamping stagnation

收录

  • EI
  • Scopus
  • SCIE

学术指纹

探究 'Mechanical fault diagnosis of outdoor high-voltage disconnector' 的科研主题。它们共同构成独一无二的学术指纹。

引用此