跳到主要导航 跳到搜索 跳到主要内容

Mechanism and risk assessment of conductors' localized breakage-fracture in high-voltage transmission lines

  • Hongliang Wu
  • , Xiaohong Li*
  • , Chengli Zhu
  • , Hong Dou
  • *此作品的通讯作者
  • Electric Power Research Institute

科研成果: 期刊稿件 › 论文 › 同行评审

摘要

The risk-based maintenance of high-voltage conductors was implemented by establishing the risk assessment model from aluminum strands' localized breakage to conductors' fracture according to the mechanical structure reliability theory. Quantitative relationships between fracture risk probabilities and breakage degree, tensile force, current, ambient temperature, heat transfer coefficient and duration time were assessed respectively based on this model. And the graded warning intervals of these risk factors were calculated according to the risk probability ranking intervals. The results show that the conductors' fracture risk probabilities increase with time in a half parabolic manner. And the threshold values corresponding to the risk probabilities are over 13.23% for breakage degree, 30% ultimate tensile strength for tensile force, 500 A for current, 35 for ambient temperature, and below 20 W/(m2·K) for heat transfer coefficient. The importance ranking of these risk factors is as follows: breakage degree, tensile force, current, ambient temperature, and heat transfer coefficient. There are level I, II, III, IV warning interval in both breakage degree and tensile force, and level I, II warning interval in current. While in conventional environment, there are only level I warning intervals in ambient temperature and heat transfer coefficient. The established quantitative risk assessment model and ranking method can provide reference for the operation safety management of transmission line conductors.
投稿的翻译标题Mechanism and risk assessment of conductors' localized breakage-fracture in high-voltage transmission lines
源语言中文
页(从-至)935-940
页数6
期刊Dongnan Daxue Xuebao (Ziran Kexue Ban)/Journal of Southeast University (Natural Science Edition)
卷44
期5
DOI
出版状态已出版 - 20 9月 2014

关键词

  • Temperature

收录

  • EI
  • Scopus

学术指纹

探究 'Mechanism and risk assessment of conductors' localized breakage-fracture in high-voltage transmission lines' 的科研主题。它们共同构成独一无二的学术指纹。

引用此