摘要
We calculated the surface electric field of electric power fittings in UHV valve hall using the electrostatic field finite element method. Firstly, we built a 3D model of ±800 kV UHV high-end valve hall. Then, we obtained the potential waveform of main equipment under rated power and light load power in the hall by PSCAD simulation by using parameters of the equipment. Finally, using instantaneous loading method of electrostatic field and typical data from the numerical solutions, we obtained the principles of the electric field distributing and the maximum electric field locating in the valve hall, and optimized the fittings where there were the maximum electric field values of the valve hall. The calculated results indicate that, the maximum surface electric field intensity of the connection and shielding fittings in Y-Y side is relatively low, meeting the control requirements of UHV valve hall electric field. However, the surface electric field intensity of the shielding fittings in Y-D side is relatively high, close to or even more than the corona onset value, thus it should be focused on, and the diameter of shielding ring for Y-D side post insulator is proposed to be 100 mm. The conclusions provide a reliable support for designing UHV valve hall, and they have important reference value.
| 投稿的翻译标题 | Numerical solution of surface electric field in ±800 kV UHVDC converter station valve hall of electric power fittings |
|---|---|
| 源语言 | 中文 |
| 页(从-至) | 2916-2923 |
| 页数 | 8 |
| 期刊 | Gaodianya Jishu/High Voltage Engineering |
| 卷 | 39 |
| 期 | 12 |
| DOI | |
| 出版状态 | 已出版 - 12月 2013 |
关键词
- Shielding
收录
- EI
- Scopus
学术指纹
探究 'Numerical solution of surface electric field in ±800 kV UHVDC converter station valve hall of electric power fittings' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver