摘要
With the development of HVDC, transmission capacity and transmission voltage level are both increasing. Under this situation, designing reliable grounding grid is more demanding. For areas with high soil resistivity, the grounding parameters can hardly meet relevant requirements. To solve this problem, this paper takes Luxi convertor station as an example to illustrate the designing process, and analyzes different design schemes. The results show that for areas with high deep soil resistivity the effect of using vertical grounding rods is slight, while the one of lengthening horizontal grounding objects is evident.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 489-496 |
| 页数 | 8 |
| 期刊 | PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON LOGISTICS, ENGINEERING, MANAGEMENT AND COMPUTER SCIENCE (LEMCS 2015) |
| 卷 | 136 |
| 出版状态 | 已出版 - 12 11月 2016 |
| 活动 | 4th International Conference on Sensors, Mechatronics and Automation (ICSMA) - Zhuhai,PEOPLES R CHINA, Zhuhai, 中国 期限: 12 11月 2016 → 13 11月 2016 |
关键词
- convertor station
- design
- grounding grid
- grounding resistance