跳到主要导航 跳到搜索 跳到主要内容

Studies on metallurgical contamination accumulation characteristics on ceramic insulator of 500 kV AC transmission line

  • Lei Lan*
  • , Lin Mu
  • , Xiaoqing Yuan
  • , Jing Yan
  • , Yu Wang
  • , Wei Wang
  • , Yang Shen
  • , Lu Hao
  • *此作品的通讯作者
  • Guizhou Power Grid Co Ltd
  • State Grid Anhui Elect Power Maintenance Branch

科研成果: 期刊稿件 › 论文 › 同行评审

10 引用 (Scopus)

摘要

The composition of metallurgical contamination is rather special, which has a great influence on the contamination accumulation and flashover characteristics of the insulators. In this study, the 500 kV AC line insulators in metallurgical industry area of central China were sampled. The ion composition, element composition, micromorphology and particle size distribution of contamination at high and low end of insulator string were tested, respectively. The equivalent salt deposit density (ESDD) and non-soluble deposit density (NSDD) of high-voltage end, low-voltage end and middle segment of three-phase insulator strings were tested. The results indicate that the contamination particles are irregular in shape and dispersed with each other. The contamination particle size of high-voltage end is larger than that of low-voltage end. The main components of the contamination are Fe2O3 and CaSO4. The ESDD and NSDD of upper surface of upper phase is lower than that of middle phase and lower phase with the cleaning of rainwater. Due to the subsidence of metallurgical contamination from high altitude, the ESDD and NSDD of lower surface of the upper phase is higher than that of middle phase and lower phase. The ESDD and NSDD of lower surface of three phases reduce with the decrease of height.
源语言英语
页(从-至)722-728
页数7
期刊IET Science, Measurement and Technology
卷13
期5
DOI
出版状态已出版 - 7月 2019

关键词

  • flashover
  • ceramic insulators
  • contamination
  • insulator testing
  • particle size
  • insulator contamination
  • power transmission lines
  • metallurgical industries
  • ESDD
  • NSDD
  • ceramic insulator
  • flashover characteristics
  • metallurgical industry area
  • ion composition
  • element composition
  • micromorphology
  • particle size distribution
  • insulator string
  • equivalent salt deposit density
  • nonsoluble deposit density
  • three-phase insulator strings
  • contamination particle size
  • metallurgical contamination
  • voltage 500
  • 0 kV
  • Fe2O3
  • CaSO4

收录

  • EI
  • Scopus
  • SCIE

学术指纹

探究 'Studies on metallurgical contamination accumulation characteristics on ceramic insulator of 500 kV AC transmission line' 的科研主题。它们共同构成独一无二的学术指纹。

引用此