@inproceedings{bb15aac226df42b8a1a638847b84be75,
title = "Test research on overvoltage withstanding characteristics of control cables",
abstract = "Withstanding characteristics of control cables under 50Hz AC, DC and lightning impulse overvoltage are tested and studied, and the results show that surface discharge voltage of cable terminal tends to saturate with the increase of the pole distance; the fact that head and shield of its are treated well or not has a great effect on the withstanding characteristic of control cables; the insulating property between shield and core wires is the most unsubstantial link in the whole insulation of control cables, which can withstand more than 18kV 50Hz AC voltage, 45kV positive polarity DC voltage and 40kV negative polarity lightning impulse voltage within 30 seconds.",
keywords = "Electric insulation, Electric potential, Electric wire, Lightning, Overvoltage protection, Surface discharges, Cable terminals, Control cables, Discharge voltage, Lightning impulse, Electric cables",
author = "Wenjun Zhou and Guangwu Deng and Jianguo Wang and Fei Xu and Lijing Wei and Bin Ma. and Hubing Zhou",
year = "2005",
month = jun,
day = "5",
language = "English",
isbn = "9784886860743",
series = "Proc Int Symp Electr Insul Mater",
pages = "816--819",
booktitle = "Proceedings of the International Symposium on Electrical Insulating Materials",
}